Check the factory jumpers before your next install

GE air handler control boards ship with factory-installed jumpers on the low-voltage terminal strip. Whether a jumper stays in or comes out depends on the air handler type and what it is paired with — and getting it wrong is the single most common cause of short cycling, no ramp-down, and backwards heating/cooling changeover on heat pump systems.

The short version
ECM air handler + heat pumpRemove the DS / R / O jumper
ECM air handler + ACLeave the DS / R / O jumper in
Variable Speed + heat pumpRemove the O–R jumper
Variable Speed + ACLeave the O–R jumper in

The full notice also covers the DS terminal on Variable Speed units (dehumidification air volume — three options) and why removing the Y1 / Y2 jumper and wiring it as a true two-stage system gets you the full compressor and blower ramping profile.

Download the notice (PDF)

Already have systems in the field? If a heat pump is short cycling, not ramping down, or showing incorrect changeover — check these jumpers first. It is usually this.